Preface
Welcome to the SK320 Series Single-Phase 220V to Three-Phase 380V VFD Selection Guide. This guide provides detailed model descriptions, technical parameters, application scenarios, selection methods, and precautions for the SK320 Series VFDs, helping you select the appropriate product model based on your actual needs to ensure stable and reliable system operation.
Table of Contents
- Product Overview
- Model Description
- Technical Parameters
- Application Scenarios
- Selection Method
- Selection Examples
- Precautions
- Installation and Maintenance
Product Overview
SK320 Series Features
The SK320 Series Single-Phase 220V to Three-Phase 380V VFD is a high-performance variable frequency drive specially designed to solve the problem of driving three-phase motors in single-phase power environments. This series adopts advanced AC-DC-AC frequency conversion technology, which can convert single-phase 220V AC power to three-phase 380V variable frequency AC power, providing a stable operating environment for three-phase motors.
Main Advantages
- Single-Phase Input, Three-Phase Output: Solves the problem of driving three-phase motors in single-phase power environments
- Vector Control Technology: Provides high-precision speed and torque control
- Wide Voltage Range: Adapts to power grid fluctuations, input voltage range: 180-260VAC
- Multiple Control Methods: Supports V/F control, open-loop vector control
- Comprehensive Protection Functions: Overload, overvoltage, undervoltage, overtemperature, short circuit and other multiple protections
- Built-in Brake Unit: Standard brake unit, optional brake resistor
- Communication Function: Supports Modbus RTU communication protocol for easy system integration
- Compact Size: Compact design saves installation space
Model Description
Model Naming Rules
|  |  | 
Special Function Code Explanation
| Code | Function Description | 
|---|---|
| N | Standard Type (No special function) | 
| H | High-Frequency Type (Maximum frequency up to 400Hz) | 
| P | Pump Special Type (Built-in PID function) | 
| F | Fan Special Type (Fan curve) | 
| M | Heavy-Duty Type (Overload capacity 150% for 1 minute) | 
Common Model List
| Model | Rated Power | Adapted Motor Power | Rated Input Current | Rated Output Current | 
|---|---|---|---|---|
| SK320-0015-N | 1.5kW | 1.5kW | 11A | 7A | 
| SK320-0022-N | 2.2kW | 2.2kW | 16A | 10A | 
| SK320-0037-N | 3.7kW | 3.7kW | 24A | 16A | 
| SK320-0055-N | 5.5kW | 5.5kW | 35A | 24A | 
| SK320-0075-N | 7.5kW | 7.5kW | 46A | 32A | 
| SK320-0110-N | 11kW | 11kW | 65A | 45A | 
Technical Parameters
Basic Parameters
| Parameter | Specification | Remarks | 
|---|---|---|
| Input Voltage | Single-Phase 220VAC | 180-260VAC wide voltage range | 
| Input Frequency | 50/60Hz | Auto-adaptive | 
| Output Voltage | Three-Phase 0-380VAC | Linearly varies with frequency | 
| Output Frequency Range | 0.1-50Hz/60Hz | Can be extended to 400Hz (H type) | 
| Frequency Resolution | Digital setting: 0.01Hz Analog setting: 0.1Hz | - | 
| Frequency Accuracy | Digital setting: ±0.01% (-10°C~+50°C) Analog setting: ±0.5% (25°C±10°C) | - | 
| Control Method | V/F control, open-loop vector control | - | 
| Starting Torque | 150% rated torque @0.5Hz (vector control) | - | 
| Overload Capacity | 150% rated current for 1 minute 200% rated current for 3 seconds | M type: 150% rated current for 2 minutes | 
Protection Functions
| Protection Type | Protection Description | 
|---|---|
| Overcurrent Protection | Protection when output current exceeds set value | 
| Overload Protection | Automatic protection when motor is overloaded | 
| Overvoltage Protection | Protection when DC bus voltage is too high | 
| Undervoltage Protection | Protection when input voltage is too low | 
| Overtemperature Protection | Protection when heatsink temperature is too high | 
| Short Circuit Protection | Quick protection when output is short-circuited | 
| Phase Loss Protection | Protection when input phase is lost | 
| Ground Protection | Motor ground fault protection | 
| Locked Rotor Protection | Protection when motor is locked | 
| Over-torque Protection | Protection when output torque exceeds set value | 
Environmental Parameters
| Parameter | Specification | Remarks | 
|---|---|---|
| Ambient Temperature | -10°C~+50°C | Derate when exceeding 40°C | 
| Relative Humidity | 5%~95% | No condensation | 
| Altitude | ≤1000m | Derate when exceeding 1000m | 
| Protection Class | IP20 | Indoor use, avoid dust and water droplets | 
| Vibration | ≤5.9m/s² (0.6g) | - | 
Communication Parameters
| Parameter | Specification | Remarks | 
|---|---|---|
| Communication Protocol | Modbus RTU | RS485 interface | 
| Communication Rate | 9600bps/19200bps/38400bps/115200bps | Configurable | 
| Data Format | 8 data bits, 1 stop bit, no parity/even parity/odd parity | Configurable | 
Application Scenarios
The SK320 Series Single-Phase 220V to Three-Phase 380V VFD is suitable for the following scenarios:
1. Home and Small Workshops
- Driving three-phase motors in single-phase power environments
- Woodworking machinery, small machine tools, textile machinery, etc.
2. Commercial Places
- Central air conditioning fans, pump control
- Commercial kitchen equipment, refrigeration equipment
3. Agricultural Applications
- Irrigation pumps, drainage equipment
- Agricultural machinery, breeding equipment
4. Temporary Power Supply Places
- Construction site temporary equipment
- Field operation equipment
5. Special Occasions
- Stage lighting equipment
- Testing equipment, laboratory equipment
Selection Method
Basic Selection Principles
- Selection Based on Motor Power: The rated power of the VFD should be greater than or equal to the rated power of the motor
- Consider Load Characteristics: Choose the appropriate VFD type based on different load types
- Consider Usage Environment: Factors such as temperature, humidity, and altitude will affect the actual output capability of the VFD
- Reserve Capacity: It is recommended that the VFD capacity be 10%-20% larger than the actual motor demand
Load Types and Selection
| Load Type | Load Characteristics | Selection Suggestion | Suitable Model | 
|---|---|---|---|
| Constant Torque Load | Torque is constant, independent of speed | VFD capacity ≥ 1.2 times motor power | M type | 
| Fan and Pump Load | Torque is proportional to the square of speed | VFD capacity ≥ motor power | F type/P type | 
| Variable Load | Load changes greatly | VFD capacity ≥ 1.5 times motor power | M type | 
| Impact Load | Load has large impact | VFD capacity ≥ 2 times motor power | M type | 
Derating Conditions
| Environmental Condition | Derating Factor | Remarks | 
|---|---|---|
| Ambient temperature 40-50°C | Derate 10% for every 5°C increase | - | 
| Altitude 1000-2000m | Derate 1% for every 100m increase | - | 
| Altitude 2000-4000m | Derate 2% for every 100m increase | - | 
| Large power voltage fluctuations | Derate 10%-20% | - | 
Selection Examples
Example 1: Woodworking Engraving Machine
Equipment Parameters:
- Spindle Motor: 3.7kW three-phase asynchronous motor
- Input Voltage: Single-Phase 220VAC
- Load Type: Variable load with certain impact
- Usage Environment: Indoor, temperature 25°C, altitude 500m
Selection Process:
- Motor Power: 3.7kW
- Load Factor: Consider variable load, take 1.5
- Calculated Capacity: 3.7kW × 1.5 = 5.55kW
- Selected Model: SK320-0075-M (7.5kW heavy-duty type)
Selection Result: SK320-0075-M
Example 2: Irrigation Pump
Equipment Parameters:
- Pump Motor: 5.5kW three-phase asynchronous motor
- Input Voltage: Single-Phase 220VAC
- Load Type: Fan and pump load
- Usage Environment: Outdoor, temperature 35°C, altitude 800m
Selection Process:
- Motor Power: 5.5kW
- Load Factor: Fan and pump load, take 1.0
- Environmental Factor: Temperature 35°C, altitude 800m, no derating required
- Selected Model: SK320-0055-P (5.5kW pump special type)
Selection Result: SK320-0055-P
Precautions
Selection Precautions
- Power Capacity Confirmation: The VFD has a large input current, ensure sufficient power capacity
- Motor Parameter Matching: Ensure the VFD matches the motor parameters
- Starting Torque Requirements: For loads requiring high starting torque, vector control mode is recommended
- Harmonic Interference: VFDs generate harmonics that may affect other equipment, filters may be required if necessary
- EMC Requirements: Confirm whether additional EMC measures are needed based on the usage scenario
Usage Limitations
- Maximum Power Limitation: SK320 series supports a maximum of 11kW
- Long-Distance Wiring: When output cables exceed 50m, it is recommended to install output reactors
- High-Temperature Environment: When temperature exceeds 40°C, derating or enhanced heat dissipation is necessary
- Continuous Overload: Long-term overload operation is not allowed
Installation and Maintenance
Installation Requirements
- Installation Direction: Install vertically to ensure good heat dissipation
- Installation Clearance: Left and right sides ≥50mm, top and bottom ≥100mm
- Ventilation Requirements: Ensure good ventilation around, no obstacles
- Grounding Requirements: Reliable grounding, grounding resistance ≤4Ω
Maintenance
- Regular Inspection: Check once a quarter
- Cleaning Maintenance: Regularly clean cooling fans and heat sinks
- Wiring Inspection: Check if terminal connections are loose
- Parameter Backup: Regularly back up parameter settings
Common Fault Handling
| Fault Phenomenon | Possible Causes | Handling Methods | 
|---|---|---|
| Cannot Start | Abnormal input power | Check power voltage and wiring | 
| Incorrect parameter settings | Restore factory settings and reset | |
| Overload Protection | Load too heavy | Reduce load or replace with larger capacity VFD | 
| Acceleration time too short | Extend acceleration time | |
| Overheat Protection | Ambient temperature too high | Enhance ventilation or derate | 
| Cooling fan failure | Replace cooling fan | |
| Overvoltage Protection | Input voltage too high | Check power grid voltage | 
| Deceleration time too short | Extend deceleration time or add braking resistor | 
Appendix
Product Dimension Diagram
[SK320 Series Product Dimension Diagram Inserted Here]
Installation Dimension Table
| Model | Width(mm) | Height(mm) | Depth(mm) | Mounting Hole Distance(mm) | 
|---|---|---|---|---|
| SK320-0015 | 140 | 200 | 150 | 120×180 | 
| SK320-0022 | 140 | 200 | 150 | 120×180 | 
| SK320-0037 | 180 | 250 | 160 | 160×230 | 
| SK320-0055 | 200 | 300 | 180 | 180×280 | 
| SK320-0075 | 230 | 350 | 200 | 210×330 | 
| SK320-0110 | 260 | 400 | 220 | 240×380 | 
Order Information